GETTING STARTED
Caution: The meter has no power-on switch, so it will be in operation as soon as you apply power.

If you power off/on the meter, or perform a hard reset (press the RESET button twice), the meter shows "RST" followed by "STRN".

RATING/PRODUCT LABEL
This label is located on top of the meter housing.

MAIN BOARD POWER JUMPERS (refer to Figure 3-1)
Important: If you want to change the factory preset jumpers, do the following steps, otherwise go to Section 3.3.

Disconnect the power from the unit before proceeding.

1. Remove the main board from the case. Refer to Section 2.6.

2.
Locate the solder jumpers W1, W2, and W3 (located near the edge of the main board alongside the transformer).

3.
If your power requirement is 115 V ac, solder jumpers W1 and W3 should be wired, but jumper W2 should not. If your power requirement is 230 V ac, solder jumper W2 should be wired, but jumpers W1 and W3 should not.
NOTE: W4 jumper is not used.

Figure 3-1 shows the location of solder jumpers W1 through W3.
Figure 3-1
Figure 3-1. Main Board Power Jumpers (W1, W2, W3)

Figure 3-2 shows the location of jumper positions on the main board.
Figure 3-2. Main Board Jumper Positions

Figure 3-3
Figure 3-3. Upper Option Board Installation

S2 jumpers are for testing purposes. Do not use as reading errors may result.

S3 jumpers are used for the following (refer to Table 3-2):
* To enable or disable the front panel push-buttons
* To allow for an extremely low resistance load for analog output
* To disable the MENU button
* To perform calibration procedure

Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors may result.


S3 Jumper Functions Table 6-1
JUMPER
DESCRIPTION
S3-A
Install to enable front panel push-buttons. Remove to disable all front panel push-buttons
S3-B
Removed. Install for meter calibration.
S3-C
Normally: Removed. Install for analog output when load is less than 1 Kohm impedance. Care should be taken when installing this jumper.
S3-D
Removed. Not used.
S3-E
If installed without S3-B, MENU locks out. If you press the MENU button, the meter shows "LOCK".

PANEL MOUNTING
1. Cut a hole in your panel, as shown in Figure 3-4.For specific dimensions refer to Figure 3-4.

2.
Insert the meter into the hole. Be sure the front bezel is flush to the panel.

3. Proceed to Section 3.4 to connect your sensor input and main power.
Figure 3-4
Figure 3-4. Meter - Exploded View
Figure 3-5

Figure 3-5
Panel Cut-Out

CONNECTING SENSOR INPUT
Figures 3-5 through 3-11 describe how to connect your sensors.
Figure 3-6
Figure 3-6
3-Wire dc Input Connections with Internal Excitation
Figure 3-7
Figure 3-7
3-Wire dc Input Connections with External Excitation

Figure 3-8
Figure 3-8
4-Wire dc Input Connections with Internal Excitation
Figure 3-9
Figure 3-9
4-Wire dc Input Connections with External Excitation


Figure 3-10

Figure 3-10
DC Current Input Connections with Internal Excitation


Figure 3-11
DC Current Input Connections with External Excitation
Figure 3-12
Figure 3-12. DC Current Input Connections with Current Source

CONNECTING MAIN POWER
Connect the ac main power connections as shown in Figure 3-12.
WARNING:
Do not connect AC power to your meter until you have completed all input and output connections. Failure to do so may result in injury!

Connect the DC main power as shown in Figure 3-13.

Main Power Connections - AC
Figure 3-13. Main Power Connections - AC

Table 3-1 shows the wire color and respective terminal connections for both USA and Europe.
AC Power Connections Table 3-2
TB1
AC POWER
WIRE COLORS
 
EUROPE
USA
7
~ AC Line Black
Brown
Black
8
~ AC Neutral
Blue
White
9
~ AC
Green/Yellow
Green

Connect the ac main power connections as shown in Figure 3-12.
Main Power Connections - DC

Figure 3-14
Main Power Connections - DC
Connect external tare connections as shown in Figure 3-14.
External Tare Connections

Figure 3-15
External Tare Connections

CONNECTING ANALOG AND RELAY OUTPUT
If you have purchased a meter with analog or dual relay output, refer to the following drawings for output connections.
Figure 3-16
Figure 3-16
Analog Output Connections
Figure 3-17
Figure 3-17
Relay Output Connections


Figure 3-18. Isolated Analog Output Connections.
Help Price List Specifications Print Manual Manuals Home
 Home Home  Table of Contents TOC  Back Back  Next Next